70,000 # HR BABCOCK & WILCOX 750 PSI WATER TUBE LO NOX NAT GAS/NO. 2 OIL SUPERHEATER
Stock Number: 103877
Click to view larger photo
Equipped With:
103877
One (1) used 1996 70,000 lb/hr Babcock & Wilcox model FM103-79 package watertube boiler, 750 PSIG design pressure, 750ºF superheat temperature, Coen Low NOx Burner set to fire Natural gas or No. 2 - 6 oil, including but not limited to the following scope of supply:
Integral completely drainable convection type superheater
Boiler trim (water column, site glass, pressure gauge, drain valves)
Feedwater stop and check valve
Blowdown valves
Continuous blowdown valve
Safety valves
Single element feedwater regulator and three-valve bypass
Coen CPF/LN-32 Low NOx burner
Moore 348 electronic combustion controller
Fireye E110 burner control w/first out annunciator
Second low water cutoff
High and low water alarms
F. D. Fan, motor drive and starter (100HP)
Soot blowers with chain drives
Connection Sizes:
Steam: 6" 600# RF Flange
Oil: 1½" NPT
Gas: 3" 150 R. F. Flange
Water: 4" 600# RF Flange
Blowdown: 1½" 600# R. F. Flange
Electrical: 460 volt, 3 ph, 60 hz
Dimensions:
Length: 30' - 10"
Width: 11' - 9"
Height: 13' - 8"